Product Selection Guide Page 683 Product Selection Guide-11th Edition

PRODUCT INFORMATION 683 PSG11 GENERAL INFORMATION Performance Data www.lithonia.com 1 FC average 0.1 FC min. 26' 3' 0.1 FC min. 1 FC average 21' 6' Example of multiple units in a row illuminating a 3' path of egress. Affinity Ext Fwd Example of multiple units in a row illuminating a 6' path of egress. 1 FC average 0.1 FC minimum AFFINITY RECOMMENDED CENTER-TO-CENTER SPACING 1,2 XENON LAMP PATH OF EGRESS 3'-WIDE PATH OF EGRESS 6'-WIDE Center-to-center spacing 26' 21' Notes 1 Meets Life Safety Code standard minimum illuminance of 0.1 FC and average illuminance of 1.0 FC. Assumes fixture is ceiling mounted in a 200'Wx200'L open area and reflectances of 80/50/20. 2 All spacings are intended to be guidelines. Results will vary if application deviates from dimensions or assumptions stated. 6' 12' 65' Example of Velare - 35W MR16 at a 12' ceiling height VELARE RECOMMENDED CENTER-TO-CENTER SPACING 1,2 LAMP TYPE 10' CEILING HEIGHT 12' CEILING HEIGHT 16' CEILING HEIGHT 20' CEILING HEIGHT H2512* 80' 75' N/A N/A H1212 17' 17' 16' H2012 36' 36' 34' H3512 65' 65' 58' 64' H5012 70' 70' H7512 130' 140' 134' 140' *VELS only Notes 1 Meets Life Safety Code standard minimum illuminance of 0.1 FC and average illuminance of 1.0 FC. Assumes open space with no obstructions, mounting height 8.5', ceiling height 9', and reflectances: 80/50/20. 2 All spacings are intended to be guidelines. Results will vary if application deviates from dimensions or assumptions stated. AFFINITY Spacing Guidelines VELARE Spacing Guidelines Performance Data PRODUCT INFORMATION 28' 20' 8.5' 3' 0.1 FC min. 1 FC average 6' LITHONIA LIGHTING EMERGENCY SYSTEMS

Previous Page