Product Selection Guide Page 1059 Product Selection Guide-11th Edition

PRODUCT INFORMATION 1059 PSG11 POWER SENTRY EMERGENCY BALLASTS Spacing Guidelines TECHNICAL INFORMATION Technical Information POWER SENTRY www.powersentrysafety.com Corridor Spacing Open Office Spacing 9' 6' 45' 1 FC average 0.1 FC minimum 9' 43' 6' 1 FC average 0.1 FC minimum Notes 1 Meets Life Safety Code standard minimum illuminance of 0.1 FC and average illuminance of 1.0 FC. Assumes three T8 lamps in each fixture, 8'W X 100' L corridor, ceiling height of 9' and reflectances of 80/50/20. 2 Meets Life Safety Code standard minimum illuminance of 0.1 FC and average illuminance of 1.0 FC. Assumes three T8 lamps in each fixture, 100'W X 100'L open office, ceiling height of 9' and reflectances of 80/50/20. PS1400QD Recommended Spacing Fluorescent battery pack: PS1400QD Fluorescent fixture: 2 x 4 parabolic Lamp type: F32T8 PS600QD Recommended Spacing Fluorescent battery pack: PS600QD Fluorescent fixture: Lensed troffer Lamp type: F32T8 POWER SENTRY RECOMMENDED CENTER-TO-CENTER SPACING FOR CORRIDORS 1 ONE FOOTCANDLE AVERAGE SPACING GUIDELINES T8 LENSED TROFFER T8 DIRECT/INDIRECT T8 PARABOLIC PS300QD 24' 18' 21' PSQ500QD 35' 28' 32' PS600QD 43' 34' 40' PS1400QD 57' 59' 53' POWER SENTRY RECOMMENDED CENTER-TO-CENTER SPACING FOR OPEN OFFICES 2 ONE FOOTCANDLE AVERAGE SPACING GUIDELINES T8 LENSED TROFFER T8 DIRECT/INDIRECT T8 PARABOLIC PS300QD 16' 13' 17' PSQ500QD 29' 21' 27' PS600QD 35' 26' 34' PS1400QD 47' 45'